- viktorcode> We're approaching a point where industry advances are answering many of the objections (the real ones, not the hysterical ones) raised by the anti-data center movement.AFAIK the main objections are against sharing the electricity bill and tax exemptions in exchange for a paltry amount of jobs created. Does the author classify those as hysterical?Also, the existence of technologies does not mean the data center next door will use them. For instance, many can run on closed water loops, but prefer not to, because it is cheaper.
- helsinkiandrewDiscussion on Nvidia blog post (429 comments) https://news.ycombinator.com/item?id=48660178I wonder if moving from 30-35 to 45 degrees has an impact on component lifespan
- iamnielsThis means that locations where the temperature never comes close to 45C are becoming much more attractive than many of the deserts where many datacenters are being built currently. Not having to pay the CAPEX and OPEX for evaporative cooling is a big difference I imagine.I have developed water cooled car electronics and there we had to work with 80C coolant with peaks to 105C. And MTBF figures had to be low, so this was a big cost driver for the design.
- GMoromisatoThis also makes orbital datacenters more economical since radiators can be smaller at higher temperatures.
- __MatrixMan__That's conveniently hot enough for a hot shower. It would be cool to see more district heating/cooling efforts.
- throw0101cASHRAE TC 9.9, "Mission Critical Facilities", members are IT folks, and they have defined a Category/Class "A4" that have dry-bulb operating temperatures in the 5-45˚C range:* https://www.upsite.com/blog/the-importance-of-mutual-underst...There's also:> For those familiar with the liquid cooling guidelines, the most obvious change will be that of the Liquid Cooling class designations. Previously, the classes were designated W1, W2, W3, W4 and W5. Each of those classes had a lower temperature limit of 2°C, while the upper limits were 17°C, 27°C, 32°C, 45°C, and Over 45°C respectively. The deficiency in the original designations didn’t really appear until the debate began over adding a class between 32°C and 45°C.> […] In the end, due to the need for enhanced flexibility, not to mention making it easier for users to remember what temperature goes with the Class, the 5th Edition redesignated the classes based on their upper temperature limit – therefore the classes are now W17, W27, W32, NEW class W40, W45, and the now named W+.* https://www.upsite.com/blog/what-you-need-to-know-about-ashr...So >35C isn't entirely unknown already.* https://www.ashrae.org/technical-resources/bookstore/datacom...* https://greencalculus.com/standards/ashrae-tc-9-9-thermal-gu...
- leni536I assume this also means more water moved for the same power and target die temperature. I wonder what other engineering considerations follow from that.
- WaterluvianAre there any Factorio-like games that treat heat gradients as a kind of spatial resource? Like in some sci fi factory you’ve got an iron smelter pressed right up against your data refinery?
- yreadDatacenters here on Earth will be much less of a problem with less water consumption because they won't need evaporative cooling
- dextrousExcellent Buggles lyric reference as the lead-in, thank you! I always post another line in these cases“I met your children. What did you tell them?”
- quickthrowmanWell, it killed the chiller for data centers that have liquid cooled racks. Which is good news, 300-350 watts per ton of cooling is better than 1000 watts per ton of cooling from a chiller.1 ton of cooling = 12,000 BTU/hr = 3.52 kW thermal coolingAir handlers in every non data center building will continue using chilled water at 45F to 55F (7C to 13C) to maintain a 55F discharge air temp setpoint during cooling.https://mitchellt.com/2018/10/23/why-is-55-so-important.htmlThe same set of companies that make chillers are the ones that make dry coolers: Carrier, Daikin, Trane, York (JCI), Liebert (Vertiv)
- ExoticPearTreeASHRAE has a maximum inlet temperature of 45 degrees Celsius. You can order Dell servers configured for this in an air-cooled design. I looked at it for places where proper AC is not readily available or best I could is a fan (mostly industrial facilities with close to no IT).The Nvidia design is not new, I think here there was a link to a paper a while back discussing the advantages of raising the liquid temperature in liquid-cooled designs.Now, keep in mind that yes, 45 degrees is quite hot for humans, but if a computer can get to 100 or 150 degrees without cooling, those 45 degrees make the liquid temperature quite cold.As a parallel, think of the fact that car cooling is done at 90 degrees Celsius. Too hot for humans, but very cool for engines.
- jeffwassWhat fraction of a typical data center’s power usage comes from the chillers?
- tomaskafkaExcellent, hyperscalers don’t need to care about climate anymore as ability to work in 45 degrees Celsius means AI will comfortably keep working through human extinction level temperatures just fine.Shareholders in climatized New Zealand bunkers rejoice.
- mvcGlad the computers will continue to be operable when their rampant use makes planet hotter. Are us humans going to get a similar upgrade?
- originiI don't get it anyway.These DC are big and create a lot of heat. Why is there nothing around them which would take that heat off them?Can't we even use a heatpump to even take it to make a higher difference for some industries etc.?Suckerburg even destroyed a CPU based DC to build it up again as a GPU based on. They can build stuff
- jfkimmesWow, this contains so many AI-isms that it is legitimately hard to read for me. Shocking to see such blatant slop in a journalistic publication (vs. a random blog post).https://www.pangram.com/history/6901a6ab-fc82-40bc-9be6-f67a...
- dist-epochSahara land suddenly becoming very valuable.
- FLeXMurphyWe haven't noticed it because we've literally been doing this for decades in non-data-center applications. Holy marketing batmans.
- cucumber3732842Sooooo... downsize everything, still run chillers and have better capex for the same-ish opex?There's no inherent reason this has to be a hard cut or that a hard cut to a different cooling architecture will be the right way to go.
- hinkley[dead]
- arjendevos[dead]
- LoganDark[dead]
- ZiiSI know it is irrational but factual documentaries like the matrix do make me think if we should optimize machines to need body temperature fluids.